10 kV Variable Frequency Series Resonant Test System
AC withstand testing of 10 kV cables, switchgear and transformers, tuning to resonance anywhere from 30 to 300 Hz.
Test methods per IEC 60076
Test methods per IEC 62271-100
Test methods per IEEE 400.2 · IEC 60502
Test methods per IEC 60060-1 · IEC 60270
Test methods per IEC 60255 · IEC 61850
Test methods per IEC 61869
Test methods per IEEE 81
Test methods per IEC 60896
810 kVA series resonant test system with two output levels, 270 kV / 3 A or 27 kV / 30 A, for AC withstand tests on cables, transformers, GIS and generators.
Compare all 9 series resonant test systems and sizing guide →
The HUAC-810kVA/270kV/27kV is a high-capacity variable frequency series resonant test system for AC withstand voltage and insulation tests on high-voltage power cables, transformers, gas-insulated switchgear (GIS) and generators in power plants, substations and high-voltage laboratories. It is built for large test objects under demanding site conditions.
The system has two output levels from the same 810 kVA rating. With the modular reactor sections connected in series it reaches 270 kV at 3 A for high-voltage, lower-capacitance objects. With the sections in parallel it delivers 27 kV at 30 A for high-capacitance objects such as long medium-voltage cables and generator windings. The control unit sweeps the frequency between 30 and 300 Hz, tracks the resonant point automatically, and displays frequency and voltage curves in real time.
See also the 216 kVA / 108 kV and 1500 kVA / 500 kV systems, or compare the full range.
| General | |
|---|---|
| Model | HUAC-810kVA/270kV/27kV |
| Rated capacity | 810 kVA |
| Output | |
| Rated voltage | 270 / 27 (dual level) kV |
| Rated current | 3 A at 270 kV / 30 A at 27 kV |
| Frequency range | 30 – 300 Hz |
| Configuration | |
| Reactors | Modular, multi-stage, series or parallel connection; detachable for transport |
| Voltage divider | Dual function: measurement and compensation |
| Protection | |
| Protection functions | Overcurrent, overvoltage, flashover discharge |
| Control | |
| Display | Large colour touch-screen LCD |
| Operating modes | Manual, automatic, semi-automatic |
| Frequency tuning | Automatic tracking and resonance calculation |
| Environment | |
| Operating temperature | -10 – 45 °C |
| Relative humidity | ≤ 85 %, non-condensing |
Specifications may change without notice. Contact us for the latest datasheet.
The datasheet and user manual for this instrument are sent on request, usually within one business day.
Both use the same 810 kVA rating. With the reactor sections in series the system delivers 270 kV at 3 A, for high-voltage objects with lower capacitance. With the sections in parallel it delivers 27 kV at 30 A, for high-capacitance objects such as long medium-voltage cables and generator windings.
AC withstand and insulation tests on high-voltage power cables, power transformers, GIS and generators, in power plants, substations and high-voltage laboratories.
Yes. The reactor is built from modular sections that are detached for transport and stacked again on site.
The system operates from -10 °C to 45 °C at a relative humidity of up to 85 % without condensation.
It depends on the capacitance of your largest test object, the test voltage and the test frequency. Send us the details, or see the sizing guide and comparison table on our series resonant test system page.
Have another question? Ask our application engineers.
Request a quote
Tell us the asset ratings and site conditions. A sales engineer will reply with a recommendation and quotation.
Related products
AC withstand testing of 10 kV cables, switchgear and transformers, tuning to resonance anywhere from 30 to 300 Hz.
Locate insulation defects in switchgear, cables and rotating machines before they fail.
XB series resonant test system, 20–300 Hz, Q > 50, distortion < 1 %, units under 40 kg, for AC withstand tests on cables, transformers, GIS and generators.
Request a quote
A sales engineer replies within one business day.Or emailsales@huactester.com.