MODEL HUAC-GKC-6

High-Voltage Switch Dynamic Characteristic Tester

Circuit breaker timing, reclosing, bounce, speed, travel and coil current tester for 12 breaks, with built-in DC 0–300 V / 20 A operating supply.

  • Opening and closing times of 12 breaks, in-phase and phase-to-phase synchronism
  • Reclosing: close-open, open-close and open-close-open with dead time
  • Bounce: closing bounce time, count, process and waveform; opening rebound
  • Speed: initial and maximum speed, time-travel curve
  • Travel: total travel, contact gap, overtravel, overshoot and rebound
  • Coil current values and waveforms
  • Built-in DC 0–300 V / 20 A supply for low-voltage operation tests
  • English user interface; English operating system available

Overview

The HUAC-GKC-6 tests the dynamic characteristics of high-voltage circuit breakers. It measures the opening and closing times of 12 breaks, synchronism within and between phases, the full reclosing sequence, contact bounce, speed, travel and coil current.

A built-in, digitally adjustable DC 0–300 V / 20 A operating supply performs low-voltage operation tests automatically and measures the actual operating voltage of the breaker.

Is this the right model?

Choose the HUAC-GKC-6 for routine timing, reclosing, bounce, travel and coil current tests on breakers with up to 12 breaks. Its operating supply starts from 0 V (DC 0–300 V, 20 A), which suits low-voltage operation tests.

Consider the HUAC-GK if you need PC software for formal reports, or the HUAC-GKC-HA for a touch screen and more communication interfaces.

Compare all models in this category.

See all circuit breaker test equipment, or send us your switchgear data and we will recommend the right instrument.

Technical specifications

Time
Range20,000.0 ms
Resolution0.01 ms
Error (200 ms range)0.01 ms ±2 digits
Error (2000 ms range)0.1 ms ±2 digits
Error (20,000 ms range)1 ms ±2 digits
Speed
Range / resolution20.00 m/s / 0.01 m/s
Error±0.1 m/s ±1 digit (0 – 2 m/s); ±0.2 m/s ±1 digit (> 2 m/s)
Coil
Current10.00 A range, 0.01 A resolution
DC output
Operating supplyDC 0 – 300 V digitally adjustable, 20 A momentary, 1 V resolution
Safety
Insulation resistance> 2 MΩ
Dielectric strength1.5 kV, 1 min to chassis
General
Interface languageEnglish

Specifications may change without notice. Contact us for the latest datasheet.

Applications

High-voltage circuit breakersCommissioning testsPeriodic maintenance

Downloads

The datasheet and user manual for this instrument are sent on request, usually within one business day.

Frequently asked questions

What does a reclosing test measure?

For close-open, open-close and open-close-open sequences it records the first opening time, the closing times and the dead time between operations.

Can it run low-voltage operation tests?

Yes. The built-in DC 0–300 V supply performs them automatically and measures the actual operating voltage.

How many breaks can it test at once?

12.

Have another question? Ask our application engineers.

Request a quote

Get pricing for the High-Voltage Switch Dynamic Characteristic Tester

Tell us the asset ratings and site conditions. A sales engineer will reply with a recommendation and quotation.

  1. We reply within one business dayA sales engineer reads your request and asks for anything missing.
  2. You get a recommendationThe right model and options, with a datasheet and quotation.
  3. No obligationAsk about lead time, shipping and payment terms before you decide.

By submitting, you agree to our Privacy Policy. We use your details only to answer this request.

Related products

Often ordered together

All Circuit Breaker Testing →
WhatsApp Get a quote
WhatsApp