Three-Phase Transformer Turns Ratio Tester (TTR), Battery Powered
Battery-powered three-phase TTR tester: ratio, vector group and polarity in about 10 seconds with one connection, ratio 0.9 to 10,000, 3.5 kg.
Test methods per IEC 60076
Test methods per IEC 62271-100
Test methods per IEEE 400.2 · IEC 60502
Test methods per IEC 60060-1 · IEC 60270
Test methods per IEC 60255 · IEC 61850
Test methods per IEC 61869
Test methods per IEEE 81
Test methods per IEC 60896
SFRA transformer winding deformation tester with built-in industrial PC: linear and segmented sweep 10 Hz–10 MHz, automatic diagnosis, Word reports.
Once a transformer is built, the inductance and capacitance of each winding are fixed, and so is its frequency response. Short circuits, transport shocks and fault currents can displace or deform the windings, which changes the frequency response. The HUAC-RZ-3000 measures this response to detect winding distortion, bulging, displacement, tilting, inter-turn short circuits and inter-phase contact.
The instrument has an integrated industrial PC, so no separate laptop is needed on site. It supports both linear and segmented frequency sweeps, and compares the three phases with each other and with historical data to grade the winding condition automatically. Results are saved as Word reports. It follows DL/T 911, the Chinese power-industry standard for frequency response analysis of transformer winding deformation.
See the full range of transformer test equipment, or send us your transformer data and we will recommend the right instrument.
| Sweep | |
|---|---|
| Linear sweep | 10 Hz – 10 MHz, 40,000 points; 0.25 / 0.5 / 1 kHz spacing |
| Segmented sweep | 0.5 kHz – 1 MHz, 2000 points |
| Measurement | |
| Amplitude range | -120 dB – +20 dB |
| Amplitude accuracy | 0.1 dB |
| Frequency accuracy | 0.01 % |
| Input / output impedance | 1 MΩ / 50 Ω |
| Same-phase repeatability | 99.9 % |
| General | |
| Instrument dimensions | 355 × 145 × 270 mm |
| Case dimensions | 410 × 360 × 350 mm |
| Total weight | 17 kg |
| Interface language | English |
Specifications may change without notice. Contact us for the latest datasheet.
The datasheet and user manual for this instrument are sent on request, usually within one business day.
Sweep frequency response analysis injects a low-voltage signal over a wide frequency range into one end of a winding and measures the response at the other end. Changes in the response reveal mechanical changes in the winding.
A baseline makes diagnosis easier, but without one the instrument compares the three phases with each other to assess the windings.
No. Only the connections to the bushings are removed; the tank stays closed.
Have another question? Ask our application engineers.
Request a quote
Tell us the asset ratings and site conditions. A sales engineer will reply with a recommendation and quotation.
Related products
Battery-powered three-phase TTR tester: ratio, vector group and polarity in about 10 seconds with one connection, ratio 0.9 to 10,000, 3.5 kg.
Fully automatic three-phase turns ratio tester with colour screen and blind test: ratio, vector group and polarity, ratio up to 10,000, battery or AC powered.
Single- and three-phase transformer turns ratio tester with vector group, blind test and built-in thermal printer. Ratio 0.9 to 5000, 4 kg, 220 V AC.
Request a quote
A sales engineer replies within one business day.Or emailsales@huactester.com.