Three-Phase Transformer Turns Ratio Tester (TTR), Battery Powered
Battery-powered three-phase TTR tester: ratio, vector group and polarity in about 10 seconds with one connection, ratio 0.9 to 10,000, 3.5 kg.
Test methods per IEC 60076
Test methods per IEC 62271-100
Test methods per IEEE 400.2 · IEC 60502
Test methods per IEC 60060-1 · IEC 60270
Test methods per IEC 60255 · IEC 61850
Test methods per IEC 61869
Test methods per IEEE 81
Test methods per IEC 60896
Measures transformer short-circuit impedance at low voltage and compares it with the nameplate to detect winding deformation. Class 0.2, 5–400 V, 0.1–20 A.
The HUAC-ZK-III measures the low-voltage short-circuit impedance of single-phase and three-phase power transformers during factory acceptance, overhaul, preventive maintenance and handover tests.
Comparing the measured short-circuit impedance (%) with the nameplate or factory value reveals winding displacement or deformation caused by transport, installation or short-circuit currents in service. The test is quick, the result is easy to interpret, and the instrument is light enough for field work.
See the full range of transformer test equipment, or send us your transformer data and we will recommend the right instrument.
| Measurement | |
|---|---|
| Voltage | 5 – 400 V, class 0.2 |
| Current | 0.1 – 20 A, class 0.2 |
| Interpretation | |
| Deviation ≤ ±2 % | Normal |
| Deviation ±2 % – ±5 % | Inspect periodically |
| Deviation > ±5 % | Take out of service for inspection |
| General | |
| Power supply | 220 V AC ±10 %, 50 Hz ±10 Hz |
| Ambient temperature | -10 – 50 °C |
| Humidity | ≤ 85 % RH |
| Interface language | English |
Specifications may change without notice. Contact us for the latest datasheet.
The datasheet and user manual for this instrument are sent on request, usually within one business day.
A change in the short-circuit impedance compared with the nameplate value means the winding geometry has changed, which points to displacement or deformation.
Within ±2 % the transformer is normal; between ±2 % and ±5 % it should be inspected periodically; beyond ±5 % it should be taken out of service and examined.
Short-circuit impedance and frequency response analysis are complementary methods for winding deformation. See our winding deformation testers for FRA.
Have another question? Ask our application engineers.
Request a quote
Tell us the asset ratings and site conditions. A sales engineer will reply with a recommendation and quotation.
Related products
Battery-powered three-phase TTR tester: ratio, vector group and polarity in about 10 seconds with one connection, ratio 0.9 to 10,000, 3.5 kg.