Three-Phase Transformer Turns Ratio Tester (TTR), Battery Powered
Battery-powered three-phase TTR tester: ratio, vector group and polarity in about 10 seconds with one connection, ratio 0.9 to 10,000, 3.5 kg.
Test methods per IEC 60076
Test methods per IEC 62271-100
Test methods per IEEE 400.2 · IEC 60502
Test methods per IEC 60060-1 · IEC 60270
Test methods per IEC 60255 · IEC 61850
Test methods per IEC 61869
Test methods per IEEE 81
Test methods per IEC 60896
Measures AC impedance and characteristic curves of generator rotors; also for single-phase transformer no-load and short-circuit tests. 600 V, 120 A, printer.
The HUAC-5315 measures the AC impedance and impedance characteristic curves of generator rotors, automatically or manually. Voltage, current, impedance, power and frequency are captured, displayed, stored and printed, with the curve scaled automatically for clear reading.
The same instrument performs no-load and short-circuit tests on single-phase transformers and volt-ampere characteristic tests on CTs, VTs and arc suppression coils. Over-voltage and over-current protection limits are set automatically from the test parameters.
See the full range of transformer test equipment, or send us your transformer data and we will recommend the right instrument.
| Measurement | |
|---|---|
| AC impedance | 0 – 1 Ω: 0.2 % FS ±2 digits; 1 – 6000 Ω: 0.2 % |
| AC voltage | 0 – 50 V: 0.2 % FS ±2 digits; 50 – 600 V: 0.2 % |
| AC current | 0 – 10 A: 0.2 % FS ±2 digits; 10 – 120 A: 0.2 % |
| Active power | 0 – 72 kW; 0.5 % FS ±2 digits (cos φ > 0.1) |
| Frequency | 40 – 75 Hz, 0.2 % |
| General | |
| Power supply | 185 – 250 V AC, 45 – 65 Hz |
| Dimensions | 415 × 225 × 200 mm |
| Weight | 5 kg |
| Interface language | English |
| Environment | |
| Conditions | -5 – 40 °C, RH < 95 % (25 °C), altitude < 2500 m |
Specifications may change without notice. Contact us for the latest datasheet.
The datasheet and user manual for this instrument are sent on request, usually within one business day.
Inter-turn short circuits in a generator rotor winding reduce its AC impedance. Comparing impedance curves with earlier results reveals these faults.
No-load and short-circuit tests on single-phase transformers, and volt-ampere characteristics of CTs, VTs and arc suppression coils.
Results print on the built-in printer, or transfer to a PC over RS232, where the software generates editable test reports.
Have another question? Ask our application engineers.
Request a quote
Tell us the asset ratings and site conditions. A sales engineer will reply with a recommendation and quotation.
Related products
Battery-powered three-phase TTR tester: ratio, vector group and polarity in about 10 seconds with one connection, ratio 0.9 to 10,000, 3.5 kg.
Fully automatic three-phase turns ratio tester with colour screen and blind test: ratio, vector group and polarity, ratio up to 10,000, battery or AC powered.
Single- and three-phase transformer turns ratio tester with vector group, blind test and built-in thermal printer. Ratio 0.9 to 5000, 4 kg, 220 V AC.